6
Each Beacon II board power is supplied by a transformer in the evaporator on which
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.
Configuration
CU
M
S
S
S
M = Master Evaporator S = Slave Evaporator CU = Condensing Unit
If there are multiple evaporators on a system, the
program for each SLAVE evaporator must be changed to
identify it as a SLAVE. To do so, press the “PROGRAM
REVIEW” button repeatedly until “SLA” appears then
use the “SELECT” knob to select “YES” then press
ENTER”. All Beacon II boards are shipped with the
factory default as a MASTER evaporator. Place all
boards in the “SERVICE” mode while you program the
setpoints to avoid errors and alarms which may cause
troubles at startup.
VERY IMPORTANT: This must be done for each slave
board.
Multiple Evaporator Configuration (Master/slave)
Up to 4 evaporators can be connected as a
master/slave conguration. DO NOT remove the room
sensor from any of the Beacon II boards.
This also applies when connected to the optional Smart
Controller.